3UF7000-1AU00-0
Basic Unit SIMOCODE pro C, PROFIBUS DP Interface 12 Mbit/s, RS 485, 4I/3O Freely Parameterizable, Us: 110…240 V AC/DC, Input for Thermistor Connection Monostable Relay Outputs
Basic unit SIMOCODE pro C
Specifications
Basic unit SIMOCODE pro C, PROFIBUS DP interface 12 Mbit/s, RS 485, 4I/3O freely parameterizable, Us: 110…240 V AC/DC, input for thermistor connection Monostable relay outputs | ||
product brand name | SIRIUS | |
product designation | Motor management system | |
design of the product | basic unit 1 | |
product type designation | SIMOCODE pro C | |
General technical data | ||
product function | ||
● bus communication | Yes | |
● data acquisition function | Yes | |
● diagnostics function | Yes | |
● password protection | Yes | |
● test function | Yes | |
● maintenance function | Yes | |
product component | ||
● input for thermistor connection | Yes | |
● digital input | Yes | |
● input for analog temperature sensors | No | |
● input for ground fault detection | No | |
● relay output | Yes | |
product extension | ||
● temperature monitoring module | No | |
● current measuring module | Yes | |
● current/voltage measuring module | No | |
● fail-safe digital I/O module | No | |
● ground-fault monitoring module | No | |
● control unit with display | No | |
● control unit | Yes | |
● analog I/O module | No | |
apparent power consumption | 5.3 VA | |
consumed active power | 2.9 W | |
insulation voltage with degree of pollution 3 at AC rated value | 300 V | |
surge voltage resistance rated value | 4 000 V | |
protection class IP | IP20 | |
shock resistance | ||
● according to IEC 60068-2-27 | 15g / 11 ms | |
● vibration resistance | 1-6 Hz / 15 mm; 6-500 Hz / 2 g | |
switching capacity current of the NO contacts of the relay outputs at AC-15 | ||
● at 24 V | 6 A | |
● at 120 V | 6 A | |
● at 230 V | 3 A | |
switching capacity current of the NO contacts of the relay outputs at DC-13 | ||
● at 24 V | 2 A | |
● at 60 V | 0.55 A | |
● at 125 V | 0.25 A | |
mechanical service life (switching cycles) typical | 10 000 000 | |
electrical endurance (switching cycles) typical | 100 000 | |
buffering time in the event of power failure | 0.05 s | |
reference code according to IEC 81346-2 | F | |
continuous current of the NO contacts of the relay outputs | ||
● at 50 °C | 6 A | |
● at 60 °C | 5 A | |
type of input characteristic | Type 1 in accordance with EN 61131-2 | |
Substance Prohibitance (Date) | 05/01/2012 | |
certificate of suitability | ||
● according to ATEX directive 2014/34/EU | BVS 06 ATEX F001 | |
explosion device group and category according to ATEX directive 2014/34/EU | II (2) G, II (2 ) D, I (M2) | |
Electromagnetic compatibility | ||
EMC emitted interference according to IEC 60947-1 | class A | |
EMC immunity according to IEC 60947-1 | corresponds to degree of severity 3 | |
conducted interference | ||
● due to burst according to IEC 61000-4-4 | 2 kV (power ports) / 1 kV (signal ports) | |
● due to conductor-earth surge according to IEC 61000-4-5 | 2 kV | |
● due to conductor-conductor surge according to IEC 61000-4-5 | 1 kV | |
● due to high-frequency radiation according to IEC 61000-4-6 | 10 V | |
field-based interference according to IEC 61000-4-3 | 10 V/m | |
electrostatic discharge according to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge | |
conducted HF interference emissions according to CISPR11 | corresponds to degree of severity A | |
field-bound HF interference emission according to CISPR11 | corresponds to degree of severity A | |
Inputs/ Outputs | ||
product function | ||
● parameterizable inputs | Yes | |
● parameterizable outputs | Yes | |
number of inputs | 4 | |
● for thermistor connection | 1 | |
number of digital inputs with a common reference potential | 4 | |
digital input version type 1 acc. to IEC 61131 | Yes | |
input voltage at digital input at DC rated value | 24 V | |
number of outputs | 3 | |
number of semiconductor outputs | 0 | |
number of outputs as contact-affected switching element | 3 | |
switching behavior | monostable | |
type of relay outputs | Monostable | |
wire length for digital signals maximum | 300 m | |
wire length for thermistor connection | ||
● with conductor cross-section = 0.5 mm² maximum | 50 m | |
● with conductor cross-section = 1.5 mm² maximum | 150 m | |
● with conductor cross-section = 2.5 mm² maximum | 250 m | |
Protective and monitoring functions | ||
product function | ||
● asymmetry detection | Yes | |
● blocking current evaluation | Yes | |
● power factor monitoring | No | |
● ground fault detection | Yes | |
● phase failure detection | Yes | |
● phase sequence recognition | No | |
● voltage detection | No | |
● monitoring of number of start operations | Yes | |
● overvoltage detection | No | |
● overcurrent detection 1 phase | Yes | |
● undervoltage detection | No | |
● undercurrent detection 1 phase | Yes | |
● active power monitoring | No | |
product function | ||
● current detection | Yes | |
● overload protection | Yes | |
● evaluation of thermistor motor protection | Yes | |
total cold resistance number of sensors in series maximum | 1.5 kΩ | |
response value of thermoresistor | 3 400 … 3 800 Ω | |
● of the short-circuit control | 9 Ω | |
release value of thermoresistor | 1 500 … 1 650 Ω | |
Motor control functions | ||
product function | ||
● parameterizable overload relay | Yes | |
● circuit breaker control | Yes | |
● direct start | Yes | |
● reverse starting | Yes | |
● star-delta circuit | No | |
● star-delta reversing circuit | No | |
● Dahlander circuit | No | |
● Dahlander reversing circuit | No | |
● pole-changing switch circuit | No | |
● pole-changing switch reversing circuit | No | |
● slide control | No | |
● valve control | No | |
Communication/ Protocol | ||
● protocol is supported PROFIBUS DP protocol | Yes | |
● protocol is supported PROFINET IO protocol | No | |
● protocol is supported PROFIsafe protocol | No | |
● protocol is supported Modbus RTU | No | |
● protocol is supported EtherNet/IP | No | |
● protocol is supported OPC UA Server | No | |
● protocol is supported LLDP | No | |
● protocol is supported Address Resolution Protocol (ARP) | No | |
● protocol is supported SNMP | No | |
● protocol is supported HTTPS | No | |
● protocol is supported NTP | No | |
● protocol is supported Media Redundancy Protocol (MRP) | No | |
● product function is supported Device Level Ring (DLR) | No | |
number of interfaces | ||
● according to PROFINET | 0 | |
● according to PROFIBUS | 1 | |
● according to Ethernet/IP | 0 | |
product function | ||
● web server | No | |
● shared device | No | |
● at the Ethernet interface Autocrossover | No | |
● at the Ethernet interface Autonegotiation | No | |
● at the Ethernet interface Autosensing | No | |
● is supported PROFINET system redundancy | No | |
● supports PROFIenergy measured values | No | |
● supports PROFIenergy shutdown | No | |
transfer rate maximum | 12 Mbit/s | |
identification & maintenance function | ||
● I&M0 – device-specific information | Yes | |
● I&M1 – higher level designation/location designation | Yes | |
● I&M2 – installation date | Yes | |
● I&M3 – comment | Yes | |
type of electrical connection of the communication interface | 9-pin SUB-D socket (12 Mbit) / screw terminal (1.5 Mbit) | |
Installation/ mounting/ dimensions | ||
mounting position | any | |
fastening method | screw and snap-on mounting | |
height | 111 mm | |
width | 45 mm | |
depth | 95 mm | |
required spacing | ||
● top | 40 mm | |
● bottom | 40 mm | |
● left | 0 mm | |
● right | 0 mm | |
Connections/ Terminals | ||
product component removable terminal for auxiliary and control circuit | Yes | |
type of connectable conductor cross-sections | ||
● solid | 1x (0.5 … 4.0 mm²), 2x (0.5 … 2.5 mm²) | |
● finely stranded with core end processing | 1x (0.5 … 2.5 mm²), 2x (0.5 … 1.5 mm²) | |
● at AWG cables solid | 1x (20 … 12), 2x (20 … 14) | |
● at AWG cables stranded | 1x (20 … 14), 2x (20 … 16) | |
tightening torque with screw-type terminals | 0.8 … 1.2 N·m | |
tightening torque [lbf·in] with screw-type terminals | 7 … 10.3 lbf·in | |
type of connectable conductor cross-sections for PROFIBUS wire | 2x 0.34 mm², AWG 22 | |
Ambient conditions | ||
installation altitude at height above sea level | ||
● 1 maximum | 2 000 m | |
● 2 maximum | 3 000 m; max. +50 °C (no protective separation) | |
● 3 maximum | 4 000 m; max. +40 °C (no protective separation) | |
ambient temperature | ||
● during operation | -25 … +60 °C | |
● during storage | -40 … +80 °C | |
● during transport | -40 … +80 °C | |
environmental category | ||
● during operation according to IEC 60721 | 3K6 (no formation of ice, no condensation, relative humidity 10 … 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 | |
● during storage according to IEC 60721 | 1K6 (no condensation, relative humidity 10 … 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4 | |
● during transport according to IEC 60721 | 2K2, 2C1, 2S1, 2M2 | |
relative humidity | ||
● during operation | 5 … 95 % | |
contact rating of auxiliary contacts according to UL | B300 / R300 | |
Short-circuit protection | ||
design of short-circuit protection per output | Fuse links: gG 6 A, quick-response 10 A (IEC 60947-5-1), miniature circuit-breaker C char.: 1.6 A (IEC 60947-5-1) or 6 A (I_K < 500 A) | |
Safety related data | ||
touch protection against electrical shock | finger-safe | |
Galvanic isolation | ||
(electrically) protective separation according to IEC 60947-1 | All circuits with protective separation (double creepage paths and clearances), the information in the “Protective Separation” test report, No. A0258, must be observed (link see further information) | |
Control circuit/ Control | ||
product function soft starter control | No | |
type of voltage of the control supply voltage | AC/DC | |
control supply voltage at AC | ||
● at 50 Hz rated value | 110 … 240 V | |
● at 60 Hz rated value | 110 … 240 V | |
control supply voltage frequency | ||
● 1 rated value | 50 Hz | |
● 2 rated value | 60 Hz | |
relative symmetrical tolerance of the control supply voltage frequency | 5 % | |
control supply voltage at DC | ||
● rated value | 110 … 240 V | |
operating range factor control supply voltage rated value at DC | ||
● initial value | 0.85 | |
● full-scale value | 1.1 | |
operating range factor control supply voltage rated value at AC at 50 Hz | ||
● initial value | 0.85 | |
● full-scale value | 1.1 | |
operating range factor control supply voltage rated value at AC at 60 Hz | ||
● initial value | 0.85 | |
● full-scale value | 1.1 | |
inrush current peak | ||
● at 240 V | 3 A | |
duration of inrush current peak | ||
● at 240 V | 1 ms |